Housing installation

Damage to unit/functional problems in the event of rubbing impeller.

  1. Do not fit flange sleeve either twisted or crushed.
  2. Make sure that the surface is flat.

When installing the FE 100/1 window installation kit or the ECA-DR spacing frame, see the associated installation instructions at www.maico-ventilatoren.com.

  1. Insert housing into wall breakthrough/wall sleeve (TOP).

3

Cable grommet

 

  1. Align housing horizontally and mark both dowel holes, see arrow.
  2. Drill dowel holes with a Ø of 6 mm and insert dowels.
  3. Push cable grommet carefully out of housing and remove it.
  4. Danger of short-circuits and damage to the unit. Water will penetrate if the power cable is incorrectly fed into the fan housing or if the cable grommet is not fitted correctly.

    1. Cut off cable grommet cap such that the cable grommet fits tightly round the power cable. Cut a minimum of 5 mm off the cap (power cable can bend better and electronics cover can be positioned correctly).
    2. Fit cable grommet correctly, seal on site if required.
  5. Insert cable grommet into housing.
  6. Feed power cable into the terminal compartment such that the cable grommet fits around the cable sheathing completely and does not penetrate too far into the terminal compartment.
  7. Insert housing into wall breakthrough/wall sleeve and secure with two screws. Do not insert the housing such that it is twisted or crushed. Make sure you use mounting material which is sized for the purpose.